| AWG Size | Dielectric/ Copper Wire Temperature | ||||
|---|---|---|---|---|---|
| @ 105°C | @ 80°C | @ 125°C | @ 90°C | @ 200°C | |
| 26 | 5 | 4 | 6 | 5 | 7 |
| 30 | 3 | 2 | 3 | 3 | 4 |
| 24 | 7 | 6 | 8 | 7 | 10 |
| 28 | 4 | 3 | 5 | 4 | 6 |
| 20 | 13 | 10 | 14 | 12 | 17 |
| 22 | 10 | 8 | 11 | 9 | 13 |
| 16 | 24 | 29 | 26 | 22 | 32 |
| 18 | 18 | 15 | 20 | 17 | 24 |
| 12 | 45 | 36 | 50 | 40 | 55 |
| 14 | 33 | 27 | 40 | 30 | 45 |
| 10 | 58 | 47 | 70 | 55 | 75 |
Table of contents
- Key Determinants of Current Carrying Capacity of Copper Conductors
- Annealed Bare Copper Wire Specification
- Bundled Conductors Derating Factors
- Methods to Calculate the Cable and Current Carrying Capacity
- Current Density of Copper Per sq mm
- Max Current Density of Aluminium and Copper Conductors
- Formula for The Current Carrying Capacity
- Current Capacity of an Aluminium and Copper Conductor
- Standards of Bare Copper Conductor Current Carrying Capacity
- Copper Conductor Ampacity Charts
- Current Carrying Capacity of Copper Wire Per sq mm Chart
- Current Carrying Capacity Of Aluminium Cable
- Class 2 Copper Wire Diameter Chart & Properties
- Amperes Conductor Chart
- Wire Gauge Chart
- Copper Cable Ampacity Chart
- Current Carrying Capacity of 0.5 Sq Mm Copper Wire for Single Core
- Twin and Multicore with Current Rating Copper Conductor
- Copper Wire Current Carrying Capacity for 1.5MM2 to 3.5MM2
- Current Capacity Copper Wire for 50MM2 to 400MM2
- Current Ratings Wire Gauge Sizes
- Current Carrying Capacity Copper Wire Temperature Rating
- American Wire Gauge Sizes
Key Determinants of Current Carrying Capacity of Copper
Conductors

Cpper Wire Size & Amp Ratings
| Aluminum | Copper | ||||
|---|---|---|---|---|---|
| Wire Gauge Size | 90°C (194°F) XHHW-2, THHN, THWN-2 |
75°C (167°F) THW, THWN, SE, USE, XHHW |
75°C (167°F) THW, THWN, SE, USE, XHHW |
60°C (140°F) NM-B, UF-B |
90°C (194°F) THWN-2, THHN, XHHW-2, USE-2 |
| 750 | 435 | 385 | 475 | — | 535 |
| 14 | — | — | 20 | 15 | 25 |
| 300 | 260 | 230 | 285 | — | 320 |
| 8 | 45 | 40 | 50 | 40 | 55 |
| 350 | 280 | 250 | 310 | — | 350 |
| 12 | 25 | 20 | 25 | 20 | 30 |
| 6 | 55 | 50 | 65 | 55 | 75 |
| 1000 | 500 | 445 | 545 | — | 615 |
| 10 | 35 | 30 | 35 | 30 | 40 |
| 3 | 85 | 75 | 100 | 85 | 115 |
| 4 | 75 | 65 | 85 | 70 | 95 |
| 500 | 350 | 310 | 380 | — | 430 |
| 1 | 115 | 100 | 130 | — | 145 |
| 600 | 385 | 340 | 420 | — | 475 |
| 2 | 100 | 90 | 115 | 95 | 130 |
| 2/0 | 150 | 135 | 175 | — | 195 |
| 4/0 | 205 | 180 | 230 | — | 260 |
| 1/0 | 135 | 120 | 150 | — | 170 |
| 250 | 230 | 205 | 255 | — | 290 |
| 3/0 | 175 | 155 | 200 | — | 225 |
Temperature Rating of 2000 Volts Copper Conductor for 90, 75 and 60°C
| Size | Temperature Rating of Copper (Cu)Conductor | ||
|---|---|---|---|
| (AWG or kcmil) | 75°C (167°F) | 60°C (140°F) | 90°C (194°F) |
| 12 AWG* | 25 | 30 | |
| 1500 KCMIL | 625 | 525 | 705 |
| 2/0 AWG | 175 | 145 | 195 |
| 1750 KCMIL | 650 | 545 | 735 |
| 18 AWG | — | — | 14 |
| 700 KCMIL | 460 | 385 | 520 |
| 4 AWG | 85 | 70 | 95 |
| 800 KCMIL | 490 | 410 | 555 |
| 10 AWG* | 35 | 30 | 40 |
| 16 AWG | — | — | 18 |
| 750 KCMIL | 475 | 400 | 535 |
| 3 AWG | 100 | 85 | 115 |
| 900 KCMIL | 520 | 435 | 585 |
| 2 AWG | 115 | 95 | 130 |
| 1000 KCMIL | 545 | 455 | 615 |
| 1250 KCMIL | 590 | 495 | 665 |
| 8 AWG | 50 | 40 | 55 |
| 350 KCMIL | 310 | 260 | 350 |
| 600 KCMIL | 420 | 350 | 475 |
| 6 AWG | 65 | 55 | 75 |
| 400 KCMIL | 335 | 280 | 380 |
| 4/0 AWG | 230 | 195 | 260 |
| 300 KCMIL | 285 | 240 | 320 |
| 3/0 AWG | 200 | 165 | 225 |
| 500 KCMIL | 380 | 320 | 430 |
| 1/0 AWG | 150 | 125 | 170 |
| 250 KCMIL | 255 | 215 | 290 |
| 14 AWG* | 20 | 25 | |
| 1 AWG | 130 | 110 | 145 |
| 2000 KCMIL | 665 | 555 | 750 |
Single Insulated Copper Conductors Current Carrying Capacity
| Size | Temperature Rating of Copper Conductor | ||
|---|---|---|---|
| (AWG or kcmil) | 90°C (194°F) | 60°C (140°F) | 75°C (167°F) |
| 10 AWG* | 55 | 50 | |
| 600 KCMIL | 780 | 575 | 690 |
| 4 AWG | 140 | 105 | 125 |
| 500 KCMIL | 700 | 515 | 620 |
| 3/0 AWG | 350 | 260 | 310 |
| 8 AWG | 80 | 60 | 70 |
| 700 KCMIL | 850 | 630 | 755 |
| 2 AWG | 190 | 140 | 170 |
| 400 KCMIL | 615 | 455 | 545 |
| 800 KCMIL | 920 | 680 | 815 |
| 6 AWG | 105 | 80 | 95 |
| 250 KCMIL | 455 | 340 | 405 |
| 1/0 AWG | 260 | 195 | 230 |
| 3 AWG | 165 | 120 | 145 |
| 900 KCMIL | 980 | 730 | 870 |
| 1 AWG | 220 | 165 | 195 |
| 300 KCMIL | 500 | 375 | 445 |
| 2/0 AWG | 300 | 225 | 265 |
| 350 KCMIL | 570 | 420 | 505 |
| 4/0 AWG | 405 | 300 | 360 |
| 750 KCMIL | 885 | 655 | 785 |
| 1000 KCMIL | 1055 | 780 | 935 |
| 1250 KCMIL | 1200 | 890 | 1065 |
| 1500 KCMIL | 1325 | 980 | 1175 |
| 1750 KCMIL | 1445 | 1070 | 1280 |
| 2000 KCMIL | 1560 | 1155 | 1385 |
Current-carrying Capacity From 4 to 41 Copper Conductors
| Number of current carrying conductors* | Percent of values in tables for ambient temperature |
|---|---|
| 41 and more | 35 |
| 31 – 40 | 40 |
| 21 – 30 | 45 |
| 10 – 20 | 50 |
| 7 – 9 | 70 |
| 4 – 6 | 80 |
Current-Carrying Capacity for Ambient Temperatures
| Ambient Temperature | 75°C (167°F) |
60°C (140°F) | 90°C (194°F) |
|
|---|---|---|---|---|
| 16 to 20°C | 60-68°F | 1.11 | 1.15 | 1.08 |
| 10°C or less | 50°F or less | 1.20 | 1.29 | 1.15 |
| 21 to 25°C | 69-77°F | 1.05 | 1.08 | 1.04 |
| 11 to 15°C | 51-59°F | 1.15 | 1.22 | 1.12 |
| 31 to 35°C | 87-95°F | 0.94 | 0.91 | 0.96 |
| 26 to 30°C | 78-86°F | 1.00 | 1.00 | 1.00 |
| 41 to 45°C | 105-113°F | 0.82 | 0.71 | 0.87 |
| 36 to 40°C | 96-104°F | 0.88 | 0.82 | 0.91 |
| 51-55°C | 123-131°F | 0.67 | 0.41 | 0.76 |
| 46-50°C | 114-122°F | 0.75 | 0.58 | 0.82 |
| 61-65°C | 141-149°F | 0.47 | – | 0.65 |
| 56-60°C | 132-140°F | 0.58 | – | 0.71 |
| 71-75°C | 159-167°F | – | – | 0.50 |
| 66-70°C | 150-158°F | 0.33 | – | 0.58 |
| 81-85°C | 177-185°F | – | – | 0.29 |
| 76-80°C | 168-176°F | – | – | 0.41 |
Annealed Bare Copper Wire Specification
| Specification | |
|---|---|
| Types of Current Copper Wire Carries |
A.C. Alternating Current D.C. Direct Current |
| Temperature | 30°C (86°F) |
| Benefits |
Reduce the risk of overheating maintain current carrying capacity |
Bundled Conductors Derating Factors
| Bundle | Derating Factor (X Amps) |
|---|---|
| 2-5 | 0.8 |
| 16-30 | 0.5 |
| 6-15 | 0.7 |
Methods to Calculate the Cable and Current Carrying Capacity
- Ampacity Tables
- Derating Factors
- Temperature Ratings
- Heat Generation and Dissipation
- Engineering Calculations
- Standards and Codes
- Software Tools
Current Density of Copper Per sq mm
| Anamalled Copper Wire | 3.5 A/Sq mm |
| Copper Conduits | 2.8A/Sq mm |
| Imbedded in Ground | 2A/Sq mm |
| Cable in ventilated tray | 3.0 A/Sq mm |
| Naked Copper Wire | 4.5 A/Sq mm |
Max Current Density of Aluminium and Copper Conductors
- Aluminium: Up to 3.5 A/mm²
- Copper: Up to 3.5 A/mm²
Formula for The Current Carrying Capacity

| Details | |
|---|---|
| Formula | Current (I)=Voltage (V)Resistance (R)\text{Current (I)} = \frac{\text{Voltage (V)}}{\text{Resistance (R)}} |
| Known as | Ohm’s Law |
| Current (I) | Measured in Amperes (A) |
| Voltage (V) | Measured in Volts (V) |
| Resistance (R) | Measured in Ohms (Ω) |
| Relationship | Current is directly proportional to Voltage and inversely proportional to Resistance |
Current Capacity of an Aluminium and Copper Conductor
| Cond. Area in MM | Aluminum Conductor | Copper Conductor |
|---|---|---|
| 1.5 | 13 | 16 |
| 4.0 | 23 | 25-32 |
| 2.5 | 18 | 20-25 |
| 10.0 | 40 | 63 |
| 6.0 | 30 | 40 |
| 25 | 70 | 129 |
| 16 | 51 | 98 |
| 50 | 105 | 198 |
| 35 | 86 | 158 |
| 95 | 155 | 292 |
| 70 | 130 | 245 |
| 150 | 205 | 391 |
| 120 | 180 | 344 |
| 240 | 280 | 528 |
| 185 | 240 | 448 |
| 400 | 375 | 726 |
| 300 | 315 | 608 |
| 500 | 585 | 830 |
Standards of Bare Copper Conductor Current Carrying
Capacity
- IEC 60228
- BS EN 60228
Copper Conductor Ampacity Charts
| Copper (Wire Size & Amp Ratings) | |||
|---|---|---|---|
| Wire Gauge Size | 60°C (140°F) NM-B, UF-B |
75°C (167°F) THW, THWN, SE, USE, XHHW |
90°C (194°F) THWN-2, THHN, XHHW-2, USE-2 |
| 14 | 15 | 20 | 25 |
| 12 | 20 | 25 | 30 |
| 10 | 30 | 35 | 40 |
| 8 | 40 | 50 | 55 |
| 1 | — | 130 | 145 |
| 1/0 | — | 150 | 170 |
| 2/0 | — | 175 | 195 |
| 3/0 | — | 200 | 225 |
| 6 | 55 | 65 | 75 |
| 4 | 70 | 85 | 95 |
| 3 | 85 | 100 | 115 |
| 2 | 95 | 115 | 130 |
| 4/0 | — | 230 | 260 |
| 250 | — | 255 | 290 |
| 300 | — | 285 | 320 |
| 750 | — | 475 | 535 |
| 1000 | — | 545 | 615 |
| 350 | — | 310 | 350 |
| 500 | — | 380 | 430 |
| 600 | — | 420 | 475 |
Current Carrying Capacity of Copper Wire Per sq mm Chart
| Nominal CrossSection (mm²) | Group 1 | Group 2 | Group 3 | |||
|---|---|---|---|---|---|---|
| Current Carrying Capacity(A) Copper Wire | Protective Fuse(A) | Current Carrying Capacity(A) Copper Wire | Protective Fuse(A) | Current Carrying Capacity(A) Copper Wire | Protective Fuse(A) | |
| 0,75 | 12 | 6 | 15 | 10 | ||
| 1 | 11 | 6 | 15 | 10 | 19 | 16 |
| 1,5 | 15 | 10 | 18 | 16 | 24 | 20 |
| 6 | 33 | 25 | 44 | 32 | 54 | 50 |
| 10 | 45 | 32 | 61 | 50 | 73 | 63 |
| 16 | 61 | 50 | 82 | 63 | 98 | 80 |
| 25 | 83 | 63 | 108 | 80 | 129 | 100 |
| 2,5 | 20 | 16 | 26 | 20 | 32 | 25 |
| 4 | 25 | 20 | 34 | 25 | 42 | 32 |
| 35 | 103 | 80 | 135 | 100 | 158 | 125 |
| 50 | 132 | 100 | 168 | 125 | 198 | 160 |
| 120 | 235 | 200 | 292 | 250 | 344 | 315 |
| 150 | 335 | 250 | 391 | 315 | ||
| 185 | 382 | 315 | 448 | 400 | ||
| 70 | 165 | 125 | 207 | 160 | 245 | 200 |
| 95 | 197 | 160 | 250 | 200 | 292 | 250 |
| 240 | 453 | 315 | 528 | 400 | ||
| 300 | 504 | 400 | 608 | 500 | ||
| 400 | 726 | 630 | ||||
| 500 | 830 | 630 | ||||
Current Carrying Capacity Of Aluminium Cable
Class 2 Copper Wire Diameter Chart & Properties
| NO. OF WIRES | NOMINAL CROSSSECTIONAL AREA (mm²) | DIAMETER OFCONDUCTORSmm | DIAMETER OF WIRES (mm) | MECHANICAL PROPERTIES OFPLAIN COPPER WIRE | MAXIMUM DCRESISTANCEAT 20°(ohms/km) | NOMINALWEIGHT(kg/km) | |
|---|---|---|---|---|---|---|---|
| Minimum Elongation% | Minimum TensileStrength(N/mm2) | ||||||
| 7 | 16 | 4.8 | 1.74 | 28 | 200 | 1.15 | 137 |
| 7 | 25 | 5.8 | 2.19 | 28 | 200 | 0.727 | 215 |
| 7 | 1.5 | 1.59 | 0.53 | 24 | 200 | 12.1 | 13 |
| 7 | 10 | 3.85 | 1.35 | 26 | 200 | 1.83 | 87 |
| 7 | 35 | 6.9 | 2.62 | 28 | 200 | 0.524 | 300 |
| 10 | 50 | 8.2 | 2.62 | 28 | 200 | 0.387 | 410 |
| 7 | 2.5 | 2.01 | 0.67 | 24 | 200 | 7.41 | 21 |
| 7 | 4 | 2.55 | 0.85 | 24 | 200 | 4.61 | 35 |
| 7 | 6 | 3.15 | 1.05 | 26 | 200 | 3.08 | 52 |
| 14 | 70 | 9.7 | 2.62 | 28 | 200 | 0.268 | 595 |
| 19 | 95 | 11.4 | 2.62 | 28 | 200 | 0.193 | 820 |
| 48 | 240 | 18.6 | 2.62 | 28 | 200 | 0.0754 | 2100 |
| 61 | 300 | 20.4 | 2.62 | 28 | 200 | 0.0601 | 2700 |
| 19 | 120 | 13.1 | 2.62 | 28 | 200 | 0.153 | 1040 |
| 37 | 150 | 14.2 | 2.62 | 28 | 200 | 0.124 | 1280 |
| 37 | 185 | 15.8 | 2.62 | 28 | 200 | 0.0991 | 1600 |
| 61 | 400 | 26 | 3 | 33 | 200 | 0.047 | 3400 |
| 61 | 500 | 30 | 3 | 33 | 200 | 0.0366 | 4400 |
| Insulation Materials: | Copper Temp. | 30 AWG | 28 AWG | 26 AWG | 24 AWG | 22 AWG | 20 AWG | 18 AWG | 16 AWG | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 6 AWG | 4 AWG | 2 AWG |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Polyethylene Neoprene Polyurethane Polyvinylchloride (Semi-Rigid) |
80°C | 2 | 3 | 4 | 6 | 8 | 10 | 15 | 19 | 27 | 36 | 47 | 65 | 95 | 125 | 170 |
| Polypropylene Polyethylene(High Density) | 90°C | 3 | 4 | 5 | 7 | 9 | 12 | 17 | 22 | 30 | 40 | 55 | 70 | 100 | 135 | 180 |
| Polyvinylchloride PVC (Irradiated) Nylon | 105°C | 3 | 4 | 5 | 7 | 10 | 13 | 18 | 24 | 33 | 45 | 58 | 75 | 105 | 145 | 200 |
| Kynar (135°C) Polyethylene(Crosslinked) Thermoplastic Elastomers |
125°C | 3 | 5 | 6 | 8 | 11 | 14 | 20 | 26 | 40 | 50 | 70 | 90 | 125 | 170 | 225 |
| Kapton PTFE FEP PFA Silicone |
200°C | 4 | 6 | 7 | 10 | 13 | 17 | 24 | 32 | 45 | 55 | 75 | 100 | 135 | 180 | 240 |
| BWG (UK Sizes) | Thickness (in) | Thickness (mm) | AWG (US Size) | Thickness (in) | Thickness (mm) |
|---|---|---|---|---|---|
| 30 | 0.0124 | 0.315 | 30 | 0.01 | 0.255 |
| 0 | 0.5 | 12.7 | 0 | 0.325 | 8.252 |
| 10 | 0.1406 | 3.569 | 10 | 0.12 | 3.048 |
| 24 | 0.022 | 0.559 | 24 | 0.0201 | 0.511 |
| 28 | 0.0148 | 0.376 | 28 | 0.0126 | 0.321 |
| 22 | 0.028 | 0.711 | 22 | 0.025 | 0.634 |
| 6 | 0.238 | 6.045 | 6 | 0.192 | 4.877 |
| 14 | 0.083 | 2.108 | 14 | 0.072 | 1.829 |
| 26 | 0.018 | 0.457 | 26 | 0.0159 | 0.405 |
| 18 | 0.048 | 1.219 | 18 | 0.0403 | 1.024 |
| 2 | 0.375 | 9.525 | 2 | 0.289 | 7.348 |
| 20 | 0.036 | 0.914 | 20 | 0.032 | 0.813 |
| 16 | 0.0625 | 1.588 | 16 | 0.0508 | 1.291 |
| 0 | 0.75 | 19.05 | 0 | 0.46 | 11.684 |
| 12 | 0.109 | 2.769 | 12 | 0.094 | 2.392 |
| 8 | 0.18 | 4.572 | 8 | 0.148 | 3.759 |
| 0 | 0.625 | 15.875 | 0 | 0.375 | 9.525 |
| 4 | 0.3 | 7.62 | 4 | 0.22 | 5.588 |
| SUGGESTED AMPACITIES | |||||||
|---|---|---|---|---|---|---|---|
| AMPERES PER CONDUCTOR | |||||||
| AWG | 105°C | 80°C | 125°C | 90°C | 150°C | 250°C* | 200°C |
| 30 | 3 | 2 | 3 | 3 | 3 | 4 | 4 |
| 24 | 7 | 6 | 8 | 7 | 8 | 11 | 10 |
| 28 | 4 | 3 | 5 | 4 | 5 | 6 | 6 |
| 20 | 13 | 10 | 14 | 12 | 15 | 19 | 17 |
| 26 | 5 | 4 | 6 | 5 | 6 | 8 | 7 |
| 18 | 18 | 15 | 20 | 16 | 22 | 29 | 24 |
| 22 | 10 | 8 | 11 | 9 | 12 | 14 | 13 |
| 14 | 33 | 20 | 40 | 25 | 40 | 39 | 45 |
| 16 | 24 | 18 | 26 | 20 | 29 | 37 | 32 |
| 10 | 58 | 35 | 70 | 40 | 70 | 73 | 75 |
| 12 | 45 | 25 | 50 | 30 | 50 | 54 | 55 |
Current Carrying Capacity of 0.5 Sq Mm Copper Wire for Single Core
|
For pvc non-armoured copper cable |
||||||||
|---|---|---|---|---|---|---|---|---|
| Conductor | Clipped Direct to a Surface or on a Cable TrayBunched or Unenclosed |
Bunched & Enclosed in Conduit or Trunking | ||||||
| Nominal Cross-Sectional Area (mm²) | No. and Diameter of Wires | Current Rating (A) | Volt Drop per Amp per Metre (mV) | Current Rating (A) | Volt Drop per Amp per Metre (mV) | Current Rating (A) | Volt Drop per Amp per Metre (mV) | Current Rating (A) |
| 2.5 Sq mm | 1/1.78 | 16 | 23 | 14 | 20 | 16 | 18 | 14 |
| 1.0 Sq mm | 1/1.13 | 40 | 13 | 35 | 12 | 40 | 11 | 35 |
| 4 Sq mm | 7/0.85 | 10 | 30 | 8.8 | 27 | 10 | 24 | 8.8 |
| 1.5 Sq mm | 1/1.38 | 27 | 16 | 23 | 15 | 27 | 13 | 23 |
| 10 Sq mm | 7/1.35 | 4.0 | 51 | 3.5 | 46 | 4.0 | 42 | 3.5 |
| 6 Sq mm | 7/1.04 | 6.8 | 38 | 5.9 | 34 | 6.8 | 31 | 5.9 |
| 25 Sq mm | 7/2.14 | 1.6 | 89 | 1.4 | 80 | 1.6 | 73 | 1.4 |
| 16 Sq mm | 7/1.70 | 2.6 | 68 | 2.2 | 61 | 2.6 | 56 | 2.2 |
| 50 Sq mm | 19/1.78 | 0.93 | 175 | 0.82 | 160 | 0.97 | 145 | 0.84 |
| 35 Sq mm | 19/1.53 | 1.2 | 109 | 1.0 | 98 | 1.2 | 90 | 1.0 |
| 95 Sq mm | 19/2.52 | 0.48 | 270 | 0.45 | 240 | 0.56 | 230 | 0.48 |
| 70 Sq mm | 19/2.14 | 0.65 | 220 | 0.59 | 200 | 0.71 | 185 | 0.62 |
Twin and Multicore with Current Rating Copper Conductor
| Conductor | Clipped Direct to a Surface unenclosed | Enclosed in Conduit or Trunking | |||||||
|---|---|---|---|---|---|---|---|---|---|
| Nominal Cross-Sectional Area | No. and Diameter of Wires | One Three-Core Cable one 4-core 3-phase | One Twin Cable Single-Phase A.C. or D.C. | One Three Core Cable conductor, 4 core, | One Twin Cable Conductor, Single-Phase A.C. or D.C. | ||||
| Volt Drop per amp. per metre* | Current Rating | Volt Drop per amp. per metre* | Current Rating | Volt Drop per amp. per metre* | Current Rating | Volt Drop per amp. per metre* | Current Rating | ||
| mm2 | mm | mV | A | mV | A | mV | A | mV | A |
| 2.5 + | 1/1.78 | 16 | 21 | 14 | 18 | 14 | 16 | 16 | 18 |
| 10 + | 7/1.35 | 4 | 48 | 3.5 | 41 | 3.5 | 37 | 4 | 40 |
| 6 + | 7/1.04 | 6.8 | 35 | 5.9 | 30 | 5.9 | 27 | 6.8 | 30 |
| 1.0 + | 1/1.13 | 40 | 12 | 35 | 10 | 35 | 9 | 40 | 11 |
| 4 + | 7/0.85 | 10 | 27 | 8.8 | 24 | 8.8 | 22 | 10 | 24 |
| 16 + | 7/1.70 | 2.6 | 64 | 2.2 | 54 | 2.2 | 47 | 2.6 | 53 |
| 1.5 + | 1/1.38 | 27 | 15 | 23 | 13 | 23 | 12 | 27 | 13 |
| 35 ++ | 19/1.53 | 1.2 | 87 | 1 | 72 | 1 | 65 | 1.2 | 74 |
| 25 ++ | 7/2.14 | 1.7 | 71 | 1.5 | 62 | 1.5 | 53 | 1.7 | 60 |
Copper Wire Current Carrying Capacity for 1.5MM2 to 3.5MM2
| Conductor | Defined Conditions | Clipped Direct to a Surface or on aCable Tray, and Unenclosed |
|||||||
|---|---|---|---|---|---|---|---|---|---|
| Construction | Nominal Area | One Twin Cable, Single-Phase A.C. / D.C. | Four-Core or One Three Cable, Three Phase | Four-Core or One Three Cable, Three Phase | One Twin Cable, Single-Phase A.C. / D.C. | ||||
| Volt Drop /Amp. Per m* | Current Rating | Volt Drop Per m* per Amp. | Current Rating | Volt Drop Per m* per Amp. | Current Rating | Volt Drop Per m* per Amp. | Current Rating | ||
| mm | mm2 | mV | A | mV | A | mV | A | mV | A |
| 7/0.85 | 4 | – | – | – | – | 11 | 26 | 9.1 | 22 |
| 1/1.38 | 1.5 | – | – | – | – | 28 | 14 | 24 | 13 |
| 7/1.04 | 6 | 7 | 38 | 6 | 32 | 7 | 32 | 6 | 28 |
| 3/1.04 | 2.5 | – | – | – | – | 17 | 20 | 15 | 17 |
| 7/1.70 | 16 | 2.6 | 68 | 2.2 | 58 | 2.6 | 58 | 2.2 | 50 |
| 7/1.35 | 10 | 4.1 | 52 | 3.6 | 44 | 4.1 | 45 | 3.6 | 38 |
| 19/1.53 | 35 | 1.2 | 112 | 1 | 94 | 1.2 | 93 | 1 | 80 |
| 7/2.14 | 25 | 1.7 | 91 | 1.5 | 77 | 1.7 | 76 | 1.5 | 66 |
Current Capacity Copper Wire for 50MM2 to 400MM2
| Conductor | Defined Conditions | Clipped Direct to a Surface or on a Cable Tray, and Unenclosed |
|||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Nominal Area | Construction | One Twin Cable | Four Core Cable | Single Phase A.C. or D.C. | Three or FourCore Cable | ||||||
| Current Rating | Volt Drop per Amp. Per meter* | Volt Drop per Amp. Per meter* | Current Rating | Current Rating | Volt Drop per Amp. Per meter* | Volt Drop per Amp. Per meter* | Current Rating | ||||
| D.C. | A.C. | D.C. | A.C. | ||||||||
| mm2 | mm | amp | mV | mV | mV | amp | amp | mV | mV | mV | amp |
| 50 | 19/1.78 | 180 | 0.92 | 0.92 | 0.81 | 155 | 150 | 0.92 | 0.92 | 0.81 | 125 |
| 70 | 19/2.14 | 220 | 0.64 | 0.65 | 0.57 | 190 | 180 | 0.64 | 0.65 | 0.57 | 155 |
| 95 | 19/2.52 | 270 | 0.46 | 0.48 | 0.42 | 230 | 225 | 0.46 | 0.48 | 0.42 | 190 |
| 120 | 37/2.03 | 310 | 0.36 | 0.4 | 0.34 | 270 | 260 | 0.36 | 0.4 | 0.34 | 220 |
| 150 | 37/2.25 | 355 | 0.25 | 0.32 | 0.29 | 310 | 290 | 0.25 | 0.32 | 0.29 | 250 |
| 185 | 37/2.52 | 410 | 0.23 | 0.29 | 0.24 | 350 | 340 | 0.23 | 0.29 | 0.24 | 290 |
| 240 | 61/2.25 | 485 | 0.18 | 0.25 | 0.2 | 420 | 400 | 0.18 | 0.25 | 0.2 | 350 |
| 300 | 61/2.52 | 550 | 0.14 | 0.23 | 0.18 | 475 | 460 | 0.14 | 0.23 | 0.18 | 400 |
| 400 | 61/2.85 | 620 | 0.11 | 0.22 | 0.17 | 550 | 520 | 0.11 | 0.22 | 0.17 | 460 |
Current Ratings Wire Gauge Sizes
| AWG | Diameter (in) |
Diameter (mm) |
Square (mm2) |
Resistance Aluminum (ohm/1000ft) (ohm/1000m) |
Typical Maximum. Current Load Ratings Copper amps | ||||
|---|---|---|---|---|---|---|---|---|---|
| Multicore | |||||||||
| 4 – 6 cores | up to 3 cores | 25 – 42 cores | 25 – 42 cores | 7 – 24 cores | |||||
| 34 | 0.0063 | 0.16 | 0.020 | 1325 | |||||
| 2 | 0.26 | 6.5 | 33.6 | 0.79 | 76 | 95 | 57 | 57 | 66 |
| 3 | 26.7 | 0.99 | 64 | 80 | 48 | 48 | 56 | ||
| 24 | 0.020 | 0.51 | 0.20 | 133 | 1.6 | 2 | 1.2 | 1.2 | 1.4 |
| 35 | 0.0056 | 0.14 | 0.015 | 1767 | |||||
| 28 | 0.013 | 0.33 | 0.080 | 331 | |||||
| 32 | 0.0080 | 0.20 | 0.031 | 855 | |||||
| 8 | 0.13 | 3.3 | 8.3 | 3.2 | 32 | 40 | 24 | 24 | 28 |
| 26 | 0.016 | 0.41 | 0.13 | 204 | |||||
| 1 | 0.29 | 7.4 | 42.4 | 0.63 | 88 | 110 | 66 | 66 | 77 |
| 27 | 0.014 | 0.36 | 0.096 | 276 | |||||
| 4 | 0.20 | 5.2 | 21.2 | 1.3 | 56 | 70 | 42 | 42 | 49 |
| 18 | 0.040 | 1.0 | 0.82 | 32 | 5.6 | 7 | 4.2 | 4.2 | 4.9 |
| 16 | 0.051 | 1.3 | 1.3 | 20 | 8.0 | 10 | 6.0 | 6.0 | 7.0 |
| 25 | 0.018 | 0.45 | 0.16 | 166 | |||||
| 13 | 0.072 | 1.8 | 2.6 | 10 | |||||
| 22 | 0.025 | 0.64 | 0.33 | 80 | 2.4 | 3 | 1.8 | 1.8 | 2.1 |
| 20 | 0.032 | 0.81 | 0.50 | 53 | 4.0 | 5 | 3.0 | 3.0 | 3.5 |
| 10 | 0.10 | 2.6 | 5.3 | 5.0 | 24 | 30 | 18 | 18 | 21 |
| 14 | 0.064 | 1.6 | 2.1 | 13 | 12 | 15 | 9.0 | 9.0 | 10 |
| 6 | 0.17 | 4.1 | 13.3 | 2.0 | 44 | 55 | 33 | 33 | 38 |
| 12 | 0.081 | 2.1 | 3.3 | 8.0 | 16 | 20 | 12 | 12 | 14 |
Current Carrying Capacity Copper Wire Temperature Rating
| Ambient Temp (C) | Ambient Temp(F) | 450C | 250C | 200C |
|---|---|---|---|---|
| 61-70 | 142-158 | 0.96 | 0.93 | 0.90 |
| 41-50 | 106-122 | 0.99 | 0.98 | 0.97 |
| 81-90 | 177-194 | 0.93 | 0.87 | 0.83 |
| 51-60 | 124-140 | 0.99 | 0.95 | 0.94 |
| 91-100 | 195-212 | 0.92 | 0.85 | 0.72 |
| 71-80 | 160-176 | 0.95 | 0.90 | 0.87 |
| 121-140 | 249-284 | 0.86 | 0.71 | 0.61 |
| 101-120 | 213-248 | 0.89 | 0.79 | 0.71 |
| 161-180 | 321-356 | 0.81 | 0.58 | 0.35 |
| 141-160 | 285-320 | 0.84 | 0.65 | 0.50 |
| 201-225 | 393-437 | 0.74 | 0.35 | – |
| 181-200 | 357-392 | 0.78 | 0.49 | – |
| 251-275 | 483-527 | 0.65 | – | – |
| 226-250 | 439-482 | 0.69 | – | – |
| 301-325 | 573-617 | 0.55 | – | – |
| 176-300 | 528-572 | 0.60 | – | – |
| 351-375 | 663-707 | 0.42 | – | – |
| 326-350 | 618-662 | 0.49 | – | – |
| 376-400 | 708-752 | 0.34 | – | – |

| AWG | Diameter (mm) | Diameter (in) | Area (mm²) | Resistance (Ω/km) | Resistance (Ω/1000 ft) | Max Frequency (Hz) | Max Current (A) |
|---|---|---|---|---|---|---|---|
| 000 (3/0) | 10.40384 | 0.4096 | 85 | 0.202704 | 0.0618 | 160 | 239 |
| 0000 (4/0) | 11.684 | 0.46 | 107 | 0.16072 | 0.049 | 125 | 302 |
| 0 (1/0) | 8.25246 | 0.3249 | 53.5 | 0.322424 | 0.0983 | 250 | 150 |
| 00 (2/0) | 9.26592 | 0.3648 | 67.4 | 0.255512 | 0.0779 | 200 | 190 |
| 3 | 5.82676 | 0.2294 | 26.7 | 0.64616 | 0.197 | 500 | 75 |
| 1 | 7.34822 | 0.2893 | 42.4 | 0.406392 | 0.1239 | 325 | 119 |
| 4 | 5.18922 | 0.2043 | 21.2 | 0.81508 | 0.2485 | 650 | 60 |
| 2 | 6.54304 | 0.2576 | 33.6 | 0.512664 | 0.1563 | 410 | 94 |
| 6 | 4.1148 | 0.162 | 13.3 | 1.295928 | 0.3951 | 1100 | 37 |
| 5 | 4.62026 | 0.1819 | 16.8 | 1.027624 | 0.3133 | 810 | 47 |
| 8 | 3.2639 | 0.1285 | 8.37 | 2.060496 | 0.6282 | 1650 | 24 |
| 7 | 3.66522 | 0.1443 | 10.5 | 1.634096 | 0.4982 | 1300 | 30 |
| 10 | 2.58826 | 0.1019 | 5.26 | 3.276392 | 0.9989 | 2600 | 15 |
| 9 | 2.90576 | 0.1144 | 6.63 | 2.598088 | 0.7921 | 2050 | 19 |